Final | 6/15/2011 | 6/15/2011 | 6/15/2011 | P | PASS |
Bob Reichert
|
|
|
PAT Phone #: ###-#### ok final, signed card
|
Electrical Rough-In | 6/2/2011 | 6/3/2011 | 6/3/2011 | A | PASS |
Bob Reichert
|
|
|
Pat Phone #: ###-#### corrections made, ri ok
|
Electrical Rough-In | 6/2/2011 | 6/2/2011 | 6/2/2011 | P | FAIL |
Bob Reichert
|
|
|
pat Phone #: ###-#### called, left correction notice to owner and contractor, NEC 358.30 shall secure emt within 3' of box, 362.30(A) ent shall be securely supported, no tie wraps, provide 1 1/4", BCC, NEC 725.25 there shall be no cables on grid or tiles, remove abandoned cable
|