Final | 7/5/2011 | 7/5/2011 | 7/5/2011 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by ERIC CENTERS final ok
|
Electrical Rough-In | 6/15/2011 | 6/16/2011 | 6/16/2011 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by ERIC CENTERS corrections made, ri ok
|
Electrical Rough-In | 6/15/2011 | 6/15/2011 | 6/15/2011 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by ERIC CENTERS called, left correction notice, BCC no violations shall be retained, NEC 300.4(A)(1) edge of bored holes shall be 1 1/4" from edge of framing members, 362.26 there shall not be over 360 degrees total bends between pull points
|