Final | 7/27/2011 | 7/27/2011 | 7/27/2011 | P | PASS |
Jack Frank
|
|
|
bruce Phone #: ###-#### card signed ok
|
Electrical Rough-In | 6/27/2011 | 6/27/2011 | 6/27/2011 | P | PASS |
Bob Reichert
|
|
|
Warren Phone #: ###-#### corrections made, ri walls only ok
|
Electrical Rough-In | 6/23/2011 | 6/24/2011 | 6/24/2011 | A | FAIL |
Bob Reichert
|
|
|
russ Phone #: ###-#### called, corrections not made, created new violations, free length conductor, ground screws
|
Electrical Rough-In | 6/23/2011 | 6/23/2011 | 6/23/2011 | P | FAIL |
Bob Reichert
|
|
|
Russ Phone #: ###-#### please call 30 min before going out called left message, left correction notice, NEC 300.4(D) edge of cable shall be 1 1/4" from edge of framing member and not in stud valley, 330.30(A) mc shall be supported within 12" of box, 358.30(A) shall support emt within 3' of box, 250.86 shall ground metal boxes, 110.12(A) shall close unused openings, BCC no violations shall be retained-ceilings shall be per code
|