ELE-Aging Inspection | 10/11/2012 | 10/11/2012 | 10/18/2012 | | PASS |
Rock A. Hudson
|
|
|
Scope of work now covered by permit # ELE12-01540
|
Final | 10/18/2012 | 10/18/2012 | 10/18/2012 | P | PASS |
Rock A. Hudson
|
|
|
Scope of work now covered by permit # ELE12-01540
|
ELE-Aging Inspection | 7/4/2012 | 7/4/2012 | 7/5/2012 | | PASS |
Daryl DeGrange
|
|
|
still under construction
|
ELE-Aging Inspection | 3/26/2012 | 3/26/2012 | 3/29/2012 | | PASS |
Daryl DeGrange
|
|
|
still under construction
|
Permanent Service | 6/28/2011 | 6/28/2011 | 6/28/2011 | P | FAIL |
Daryl DeGrange
|
|
|
rick Phone #: ###-#### Reconnect service mask guide wires. NEC 250.56 Install 2- 8 foot ground rods six feet apart. NEC 250.64 shall install metallic connector listed for grounding & bonding where grounding electrode conductor enters service or use non-metallic connector. Check water piping to house, if metal, needs bonding to service
|
Conference | 6/27/2011 | 6/28/2011 | 6/28/2011 | A | DONE |
Daryl DeGrange
|
|
|
Rick please call 30 min before going out Phone #: ###-#### power has been off for over 12 months.
|