Permit Information
Permit NumberELE11-01416
StatusFinaled
Name ANDERSON & WOOD CONSTRUCTION
Site Address 3201 W AIRPORT WAY
Project Name 
Customer Number11-7183
ePlanReviewNo
Description
Electrical Permit - New: Boise Airport Gateway Lanscaping & Signage Electrical Work
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/21/20126/21/20126/21/2012PPASS
DetailsBob Reichert
Contact Kelly Tarter @ ###-#### Phone #: ###-#### >> Inspection requested via web by Kristopher Wilson ok final
ELE-Aging Inspection6/19/20126/19/20126/21/2012 DONE
DetailsBob Reichert
still under construction
ELE-Aging Inspection3/20/20123/20/20123/21/2012 DONE
DetailsBob Reichert
still under construction
Conference11/2/201111/2/201111/2/2011ADONE
DetailsBob Reichert
talked to contractor, and 414 about lighting and fixture mounting to boxes, don't see code violation, contractor will try to solve issues with and via general contractor, may need conference later, contact is KELLY ###-####
Final10/21/201110/21/201110/21/2011PPASS
DetailsBob Reichert
Phone #: ###-#### >> Inspection requested via web by Kristopher Wilson ok final
Final10/19/201110/20/201110/20/2011ACANC
DetailsBob Reichert
Contact Kelly Tarter 30mins prior to inspection Phone #: ###-#### >> Inspection requested via web by Kristopher Wilson called, contractor asked to cancel, had not done panel schedule, will recall when done
Final10/14/201110/17/201110/17/2011ACANC
DetailsBob Reichert
Kelly Tarter Phone #: ###-#### >> Inspection requested via web by Kristopher Wilson see p/s, shall call for final when done
Permanent Service10/17/201110/17/201110/17/2011APASS
DetailsBob Reichert
corrections made, p/s u/g n ok, shall call for final when done
Conference10/13/201110/13/201110/13/2011PDONE
DetailsBob Reichert
talked about service
Permanent Service10/6/201110/7/201110/7/2011AFAIL
DetailsBob Reichert
Service Disconnect sticker has been installed. Phone #: ###-#### >> Inspection requested via web by Kristopher Wilson called, left correction notice, NEC 230.66 equipment shall be marked to identify it as being suitable for use as service equipment, 110.12(A) shall close front opening, 408.38 enclosure shall be dead front
Permanent Service10/4/201110/5/201110/5/2011AFAIL
DetailsBob Reichert
Permanent service inspection Phone #: ###-#### >> Inspection requested via web by Kristopher Wilson called, told contractor to re-call when inspector can find service entrance listing on panel
Electrical Rough-In9/22/20119/22/20119/22/2011PPASS
DetailsDaryl DeGrange
Underground inspection. Call Kelly @ ###-####, 30 mins prior to inspection. Phone #: ###-#### >> Inspection requested via web by Kristopher Wilson rough-in ok cover underground, verified depth
Rough-In Permanent Service9/20/20119/21/20119/21/2011ANR
DetailsDaryl DeGrange
Call Kelly @ ###-####, 30 minutes prior to inspection. Phone #: ###-#### >> Inspection requested via web by Kristopher Wilson Need to have trench opened to exspose depth on 2in conduit in at least 3 locations
Rough-In Permanent Service9/19/20119/19/20119/19/2011PFAIL
DetailsBob Reichert
Please call Kelly 30mins prior to inspection to meet the inspector on the job site. Phone #: ###-#### >> Inspection requested via web by Kristopher Wilson called, left correction notice, NEC 250.24 shqall provide system grounding, 250.52(A) shall provide electrodes for grounding, 250.56 shall provide 2 electrodes 6' apart, 250.92 shall provide bond bushings, BCC shall provide equipment prior to inspection- service disconnect, shall not cover u/g prior to inspection