Temporary Service | 7/29/2011 | 7/29/2011 | 7/29/2011 | P | PASS |
Jack Frank
|
|
|
Phone #: ###-#### >> Inspection requested via web by Rick Beckman t/s o/h new ok
|
Temporary Service | 7/5/2011 | 7/6/2011 | 7/6/2011 | A | FAIL |
Bob Reichert
|
|
|
Jason Phone #: ###-#### called, left correction notice, NEC 312.5 all conductors shall have abrasion protection, 406.8(B) shall use listed weather-proof receptacles, 110.12(B) there shall be no broken parts, 408.4 shall provide circuit directory
|