Final | 10/26/2011 | 10/26/2011 | 10/26/2011 | P | PASS |
Jack Frank
|
|
|
garage code 1234 enter Phone #: ###-#### >> Inspection requested via web by Dan Rohl
|
Rough-In Permanent Service | 7/7/2011 | 7/7/2011 | 7/7/2011 | P | PASS |
Jack Frank
|
|
|
Phone #: ###-#### >> Inspection requested via web by Dan Rohl r/i p/s u/g new ok
|
Rough-In Permanent Service | 7/5/2011 | 7/6/2011 | 7/6/2011 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Dan Rohl called, left message, left correction notice, NEC 300.4(A)(1) edge of bored holes shall be 1 1/4" from edge of framing members, 334.30 shall strap nm cable within 12" of box, shall not staple flat cable on edge, 210.52(A)(1) receptacles shall be spaced such that no point along wall is over 6' from an outlet, 110.12(A) cable shall not be damaged, BCC shall terminate all conductors in boxes
|