Final | 7/25/2011 | 7/25/2011 | 7/25/2011 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey corrections made, t/s u/g n ok
|
Temporary Service | 7/22/2011 | 7/22/2011 | 7/22/2011 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey called, left correction notice, NEC 312.5 all conductors entering enclosure shall have abrasion protection,250.24(A) gec shall terminate where grounded conductor terminates at service, 250.53(G) ground rod shall be flush with or below ground, BCC shall affix job id sticker, fee due
|