Final | 8/31/2011 | 8/31/2011 | 8/31/2011 | P | PASS |
Daryl DeGrange
|
|
|
EVERYTHINGS DONE Phone #: ###-#### >> Inspection requested via web by MARK PINNEY final ok
|
Final | 8/22/2011 | 8/23/2011 | 8/23/2011 | A | CANC |
Bob Reichert
|
|
|
TIED UP ALL RELOC LIGHTING CABLES, INSTALLED KO SEALS OUTLETS ARE DONE. TOOK CARE OF ANYTHING THAT I COULD SEE THAT NEEDED TO BE DONE. MARK Phone #: ###-#### >> Inspection requested via web by MARK PINNEY see ri
|
Electrical Rough-In | 8/23/2011 | 8/23/2011 | 8/23/2011 | A | PASS |
Bob Reichert
|
|
|
ok cover ceiling only, final to be done later
|
Final | 8/19/2011 | 8/22/2011 | 8/22/2011 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by MARK PINNEY called electrician, left correction notice, NEC 330.30(B) shall strap mc cable within 12" of box, 112.12(A) shall close unused openings in boxes, 300.11 wiring shall not be supported by ceiling assembly- grid or tiles, did not check receptales, this was done as ceiling inspection only
|
Electrical Rough-In | 7/27/2011 | 7/29/2011 | 7/29/2011 | A | PASS |
Daryl DeGrange
|
|
|
ROUGH IN METEL STEEL WALLS FOR COVER Phone #: ###-#### >> Inspection requested via web by MARK PINNEY rough-in ok cover
|