Final | 9/13/2011 | 9/14/2011 | 9/14/2011 | A | PASS |
Daryl DeGrange
|
|
|
Daniel Phone #: ###-#### final ok
|
Rough-In Permanent Service | 8/3/2011 | 8/3/2011 | 8/3/2011 | P | PASS |
Doug A Poedy
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov. P/S Connect ok. Ok to cover. Asked them to get some seperation on low voltage wire.
|
Rough-In Permanent Service | 8/2/2011 | 8/3/2011 | 8/3/2011 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov called, left correction notice, NEC 300.4(A)(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 334.23 shall protect wiring within 6' of attic access, 210.52(E) shall provide outlet at front of dwelling, 314.20 boxes in walls of combustible material sjhall be flush with finished surface, QUESTION, any garage door lights,rest ok
|