Final | 5/14/2013 | 5/15/2013 | 5/15/2013 | P | PASS |
Rock A. Hudson
|
|
|
rich Phone #: ###-#### Garage final ok
|
ELE-Aging Inspection | 5/13/2013 | 5/13/2013 | 5/13/2013 | | DONE |
Rock A. Hudson
|
|
|
No answer at door. Posted correcction notice
|
ELE-Aging Inspection | 1/30/2013 | 1/30/2013 | 1/30/2013 | | DONE |
Rock A. Hudson
|
|
|
Drove by. Job looks finished. unable to make contact
|
ELE-Aging Inspection | 10/31/2012 | 10/31/2012 | 11/6/2012 | | DONE |
Rock A. Hudson
|
|
|
still under construction
|
ELE-Aging Inspection | 7/16/2012 | 7/16/2012 | 7/16/2012 | | DONE |
Daryl DeGrange
|
|
|
still under construction
|
ELE-Aging Inspection | 4/16/2012 | 4/16/2012 | 4/16/2012 | | PASS |
Daryl DeGrange
|
|
|
stll under construction
|
Electrical Rough-In | 8/12/2011 | 8/15/2011 | 8/15/2011 | A | PASS |
Daryl DeGrange
|
|
|
Rich Phone #: ###-#### rough-in ok cover unattach garage
|
Electrical Rough-In | 8/11/2011 | 8/12/2011 | 8/12/2011 | A | FAIL |
Daryl DeGrange
|
|
|
Rich Park Phone #: ###-#### sub panel not service rated,seperate neutrals and ground wires,provide main breaker, service junction box needs to be grounded
|
Conference | 8/4/2011 | 8/5/2011 | 8/5/2011 | A | DONE |
Daryl DeGrange
|
|
|
Rich ###-#### Discussed with home owner sub panel,grounding,stapling,free wire, 1 1/4 stapling from edge of framing member, GFCI protection, temperproof receptacles, inuse covers, inspection scheduling
|