Final | 8/30/2011 | 8/30/2011 | 8/30/2011 | A | PASS |
Bob Reichert
|
|
|
Key is located by gas meter Phone #: ###-#### >> Inspection requested via web by Therrin Robertson ok final, no card to sign
|
Final | 8/15/2011 | 8/15/2011 | 8/15/2011 | P | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson see ri
|
Electrical Rough-In | 8/15/2011 | 8/15/2011 | 8/15/2011 | P | PASS |
Bob Reichert
|
|
|
corrections made, ri ok walls
|
Electrical Rough-In | 8/12/2011 | 8/12/2011 | 8/12/2011 | P | FAIL |
Bob Reichert
|
|
|
Wall inspection Phone #: ###-#### >> Inspection requested via web by Therrin Robertson called, left correction notice, NEC 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing member, 330.30(B) shall secure mc cable within 12" of box
|