Final | 1/30/2012 | 1/30/2012 | 1/30/2012 | P | PASS |
Jack Frank
|
|
|
Garage code 8607 Phone #: ###-#### >> Inspection requested via web by Therrin Robertson
|
Final | 1/26/2012 | 1/27/2012 | 1/27/2012 | A | FAIL |
Jack Frank
|
|
|
Garage Code 8607 and 7373 Phone #: ###-#### >> Inspection requested via web by Therrin Robertson called correction posted 314.3 metallic fitting not allowed in nonmetallic box, 314.43 screws not allowed in in plastic box, 314.20 box shall be flush with combustible material
|
Rough-In Permanent Service | 9/6/2011 | 9/6/2011 | 9/6/2011 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson corrections made, ri ok, p/s u/g n ok
|
Rough-In Permanent Service | 9/1/2011 | 9/2/2011 | 9/2/2011 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson called, left correction notice, NEC 334.23 shall protect cables within 6' of attic accesses, 362.30 shall secure ent within 3' of termination, 312.5 shall provide abrasion protection for cables in lv cabinet, 300.4(A) edge of hole shall be 1 14" from edge of framing member, or provide nailplate, BCC approved set of plans shall be on job
|