Final | 10/21/2011 | 10/21/2011 | 10/21/2011 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov final ok correction has been done
|
Final | 10/17/2011 | 10/17/2011 | 10/17/2011 | P | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov NEC 110.3 (B) Listed equipment shall be installed and used in accordance with any instructions including in the listing. Broan 164L exhaust fan not listed for wet locations, fan installed inside shower stall
|
Electrical Rough-In | 9/26/2011 | 9/26/2011 | 9/26/2011 | P | PASS |
Daryl DeGrange
|
|
|
Heat tile inspection Phone #: ###-#### >> Inspection requested via web by daniel bibikov rough-ok cover floor heat master bathroom, corrections made
|
Electrical Rough-In | 9/23/2011 | 9/23/2011 | 9/23/2011 | P | FAIL |
Daryl DeGrange
|
|
|
Heat tile cable Phone #: ###-#### >> Inspection requested via web by daniel bibikov NEC 110.3(B) Listed equpiment shall be installed to manufactures requirement. Floor heat cabling installed too close together, will cause over heating
|
Rough-In Permanent Service | 8/18/2011 | 8/19/2011 | 8/19/2011 | A | PASS |
Doug A Poedy
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov. P/S Connect ok. Ok to cover.
|