Final | 9/13/2011 | 9/14/2011 | 9/14/2011 | A | PASS |
Daryl DeGrange
|
|
|
code is 4907 Phone #: ###-#### >> Inspection requested via web by Brad Girard final ok
|
Permanent Service | 9/1/2011 | 9/2/2011 | 9/2/2011 | A | PASS |
Bob Reichert
|
|
|
code is 4907, house is vacant. service is on side of house in the backyard Phone #: ###-#### >> Inspection requested via web by Brad Girard corrections made, p/s o/h rec ok
|
Rough-In Permanent Service | 8/30/2011 | 8/31/2011 | 8/31/2011 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### >> Inspection requested via web by Brad Girard BCC needs 2" rigid or IMC mast, 250.64(C) GEC shall be continuous from u/g water pipe to service panel, 250.119 shall not ID #6 or smaller drop to garage,334.15 (B) shall use rigid, IMC, EMT, or PVC scedule 80 too protect romex in garage 250.56 grd rods shall be 6ft apart, make sure wire in masts are sunlight resistant called
|