Final | 10/20/2011 | 10/20/2011 | 10/20/2011 | P | PASS |
Bob Reichert
|
|
|
Final. CJ is contact. Thank you Phone #: ###-#### >> Inspection requested via web by Chris Chesnut ok final, signed card
|
Electrical Rough-In | 9/14/2011 | 9/14/2011 | 9/14/2011 | P | PASS |
Bob Reichert
|
|
|
Walls and hard lids. CJ is contact name, Thank you. Phone #: ###-#### >> Inspection requested via web by Chris Chesnut walls and hard lid only ok cover
|
Electrical Rough-In | 9/7/2011 | 9/8/2011 | 9/8/2011 | A | PART |
Bob Reichert
|
|
|
Partial rough-in. CJ is contact. Walls only w/med grade. Thank you. Phone #: ###-#### >> Inspection requested via web by Chris Chesnut corrections made, ri walls only back part ok
|
Electrical Rough-In | 9/6/2011 | 9/7/2011 | 9/7/2011 | A | FAIL |
Bob Reichert
|
|
|
Partial rough-in, walls only. CJ is contact. Could you call contact in route and if we aren''t there, we will meet you. Thank you! Phone #: ###-#### >> Inspection requested via web by Chris Chesnut NEC 517, shall provide redundant grounding for exam rooms, close open ko, provide 1 1/4" for ent
|