Electrical Rough-In | 9/7/2011 | 9/8/2011 | 9/8/2011 | P | PASS |
Bob Reichert
|
|
|
todd Phone #: ###-#### conditional, shall call for final, shall remove electrical too close to hot tub, add water pipe ground, add 2nd ground rod, remove insulation from ground wire at service, change range and dryer to 4- wire, check load calculation for service, p/s u/g rec ok
|
Final | 9/8/2011 | 9/8/2011 | 9/8/2011 | P | PASS |
Bob Reichert
|
|
|
ok final
|