Final | 11/2/2011 | 11/3/2011 | 11/3/2011 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by kevin blackmon ok final
|
Rough-In Permanent Service | 9/16/2011 | 9/16/2011 | 9/16/2011 | P | PASS |
Bob Reichert
|
|
|
>> Inspection requested via mobile web by Kevin corrections made, ri ok, p/s u/g n ok
|
Rough-In Permanent Service | 9/15/2011 | 9/16/2011 | 9/16/2011 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by kevin blackmon called, left correction notice, NEC 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing member, 334.30 shall secure nm within 12" of panel, 334.23 shall protect cable within 6' of attic access, 210.52(A)(2) shall provide receptacle in 2' wall in dining room, BCC shall provide box for receptacle in bath
|