Final | 12/8/2011 | 12/9/2011 | 12/9/2011 | P | PASS |
Daryl DeGrange
|
|
|
Garage code is 6288 eneter Phone #: ###-#### >> Inspection requested via web by Zane Robertson final ok
|
Final | 12/6/2011 | 12/7/2011 | 12/7/2011 | P | FAIL |
Doug A Poedy
|
|
|
The garage code is 6288 enter Phone #: ###-#### >> Inspection requested via web by Zane Robertson. Garage doors not GFCI protected. No power for jetted tub in master.
|
Electrical Rough-In | 9/22/2011 | 9/23/2011 | 9/23/2011 | A | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Zane Robertson rough-in ok cover corections made
|
Rough-In Permanent Service | 9/21/2011 | 9/22/2011 | 9/22/2011 | A | CANC |
Doug A Poedy
|
|
|
Phone #: ###-#### >> Inspection requested via web by Zane Robertson
|
Electrical Rough-In | 9/22/2011 | 9/22/2011 | 9/22/2011 | A | FAIL |
Doug A Poedy
|
|
|
Phone #: ###-#### >> Inspection requested via web by Zane Robertson.NEC 210.52 D At least one receptacle shall be located within 3 ft of each basin. NEC 210.52 A2 Wall spacing. NEC 334.30 NM cable must be supported within 12 inches of a box.
|
Electrical Rough-In | 9/22/2011 | 9/22/2011 | 9/22/2011 | A | FAIL |
Doug A Poedy
|
|
|
Phone #: ###-#### >> Inspection requested via web by Zane Robertson. 210.52 Wall Spacing. 210.52 At least one receptacle within 3 ft of EACH basin. 334.30 NM cable needs to be supported within 12 inches.
|
Permanent Service | 9/22/2011 | 9/22/2011 | 9/22/2011 | A | PASS |
Doug A Poedy
|
|
|
Phone #: ###-#### >> Inspection requested via web by Zane Robertson. P/S connect ok.
|