Final | 12/20/2011 | 12/20/2011 | 12/20/2011 | P | PASS |
Bob Reichert
|
|
|
call for access---Neil Phone #: ###-#### corrections made, ok final
|
Final | 12/7/2011 | 12/7/2011 | 12/7/2011 | P | FAIL |
Bob Reichert
|
|
|
call for code Phone #: ###-#### >> Inspection requested via web by Neal Rumsey called, shall fix gfci in garage and bath and garage lighting receptacles, furniture in way of panel, could not check all outlets because of furniture
|
Electrical Rough-In | 10/20/2011 | 10/21/2011 | 10/21/2011 | A | PASS |
Bob Reichert
|
|
|
call for a code >> Inspection requested via web by Neal Rumsey correction made, ri ok
|
Electrical Rough-In | 10/19/2011 | 10/20/2011 | 10/20/2011 | A | FAIL |
Daryl DeGrange
|
|
|
call for access Phone #: ###-#### >> Inspection requested via web by Neal Rumsey 210.11(C) (3) Shall be no other receptacles on bathroom outlet circuit
|
Rough-In Permanent Service | 10/12/2011 | 10/12/2011 | 10/12/2011 | P | NR |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey called, 2nd trip and electrician did not cancel before arrival at site either time, fee due
|
Rough-In Permanent Service | 10/11/2011 | 10/12/2011 | 10/12/2011 | A | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey contractor called to cancel
|