Final | 3/28/2012 | 3/29/2012 | 3/29/2012 | P | PASS |
Daryl DeGrange
|
|
|
lee Phone #: ###-#### please call before going out final ok
|
Electrical Rough-In | 11/16/2011 | 11/17/2011 | 11/17/2011 | P | PASS |
Daryl DeGrange
|
|
|
lee Phone #: ###-#### corrections made, rough-in ok cover
|
Electrical Rough-In | 11/10/2011 | 11/14/2011 | 11/14/2011 | P | FAIL |
Daryl DeGrange
|
|
|
lee Phone #: ###-#### NEC 300.4 Where bored holes are less than 1 1/4 from edge of framing member shall use nail plates. NEC 300.4(A) shall staple romex at least 1 1/4 from framing member. NEC 334.30 Shall staple NM cable within 12" of box
|
Conference | 9/29/2011 | 9/30/2011 | 9/30/2011 | P | PASS |
Daryl DeGrange
|
|
|
Please 30min prior--Lee Phone #: ###-#### Discussed with home owner requirements for residential remodel, wire sizes,box fill,free wire, stapling 1 1/4 from edge of framing member, receptacle spacing, AFCI and GFCI protection, Listed WR receptacles, inuse covers
|