DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/28/20123/29/20123/29/2012PPASS
DetailsDaryl DeGrange
lee Phone #: ###-#### please call before going out final ok
Electrical Rough-In11/16/201111/17/201111/17/2011PPASS
DetailsDaryl DeGrange
lee Phone #: ###-#### corrections made, rough-in ok cover
Electrical Rough-In11/10/201111/14/201111/14/2011PFAIL
DetailsDaryl DeGrange
lee Phone #: ###-#### NEC 300.4 Where bored holes are less than 1 1/4 from edge of framing member shall use nail plates. NEC 300.4(A) shall staple romex at least 1 1/4 from framing member. NEC 334.30 Shall staple NM cable within 12" of box
Conference9/29/20119/30/20119/30/2011PPASS
DetailsDaryl DeGrange
Please 30min prior--Lee Phone #: ###-#### Discussed with home owner requirements for residential remodel, wire sizes,box fill,free wire, stapling 1 1/4 from edge of framing member, receptacle spacing, AFCI and GFCI protection, Listed WR receptacles, inuse covers