Final | 6/21/2012 | 6/22/2012 | 6/22/2012 | A | PASS |
Doug A Poedy
|
|
|
Early morning inspection is preferred! Inspect both floors - cafe & rental / dwelling. (especially item noted on previous failed inspection). If possible, please call when the inspection is complete. Thank You! Phone #: ###-#### >> Inspection requested via web by nathan palmer
|
Final | 6/19/2012 | 6/19/2012 | 6/19/2012 | P | FAIL |
Bob Reichert
|
|
|
Inspect upstairs Rental / Dwelling - 2nd floor. Inspect Cafe - 1st floor. Reinspect service - upgraded wire to 250 MCM & 200A breaker. (Previously bought wrong wire for 200A.) Phone #: ###-#### >> Inspection requested via web by nathan palmer met contractor, he wrote list, shall not have foreign piping in dedicated and work space about panels, shall provide light in mechanical room, tighten receptacle in bath, provide gec id at incoming water pipe, shall demo old wiring, shall mount showroom receptacles, not blank off, shall bond hot and cold water pipes and provide disconnect at upstairs water heater
|
Rough-In Permanent Service | 4/25/2012 | 4/26/2012 | 4/26/2012 | A | PASS |
Jack Frank
|
|
|
Permanent Service Inspection needed for Idaho Power hook up. 1" water pipe bonded in basement + 2 ground rods driven. Phone #: ###-#### >> Inspection requested via web by nathan palmer p/s o/h new ok
|
Electrical Rough-In | 3/2/2012 | 3/5/2012 | 3/5/2012 | A | PASS |
Jack Frank
|
|
|
Nathan Phone #: ###-#### ok needs to grd mudring, install show window recepts, sign circuit, address recepts in laundry rm
|
Electrical Rough-In | 2/29/2012 | 3/1/2012 | 3/1/2012 | A | FAIL |
Daryl DeGrange
|
|
|
Requesting rough-in inspection of both: cafe - 1st floor commercial, and 2nd floor dwelling space. Seeking approval for cover. Phone #: ###-#### >> Inspection requested via web by nathan palmer NEC 334.12 can not install MC cable inside 2x4 steel studs, subject to physical damage
|
Conference | 1/17/2012 | 1/18/2012 | 1/18/2012 | P | DONE |
Jack Frank
|
|
|
Questions regarding wiring methods for the Residence above a Cafe (NM Cable vs. commercial wiring) etc. May be available AM but not guaranteed. Phone #: ###-#### >> Inspection requested via web by nathan palmer
|