Final | 11/22/2011 | 11/22/2011 | 11/22/2011 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn ok final
|
Final | 11/18/2011 | 11/21/2011 | 11/21/2011 | A | NH |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn called, will recall
|
Rough-In Permanent Service | 10/21/2011 | 10/21/2011 | 10/21/2011 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn corrections made, ri ok, check receptacle space in living room at final, p/s u/g n ok
|
Rough-In Permanent Service | 10/20/2011 | 10/20/2011 | 10/20/2011 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn called, left correction notice, NEC 110.26(F)(1)(a) there shall be no foreign piping systems in dedicated electrical space, 334.30 shall staple nm cable wirhin 12" of panel, 210.52(A)(1) no point along floor line shall be over 6' from outlet,334.23 shall protect cable within 6' of attic access
|