ELE-Aging Inspection | 2/27/2013 | 2/27/2013 | 2/27/2013 | | DONE |
Rock A. Hudson
|
|
|
2nd attempt to call contractor, left message
|
ELE-Aging Inspection | 11/28/2012 | 11/28/2012 | 11/28/2012 | | DONE |
Rock A. Hudson
|
|
|
Called contractor and left message
|
Permanent Service | 11/7/2011 | 11/7/2011 | 11/7/2011 | P | FAIL |
Daryl DeGrange
|
|
|
There hasn''t been a meter at this location for over a year, Idaho Power is requiring an inspection of the service before powering. Access code is 9771, thanks. Phone #: ###-#### >> Inspection requested via web by Stephen Kren Service grounding requires 2 eight foot ground rods six feet apart unless proven 25 ohms or less of resistance. Rerun grounding conductor through non-conductive connector. Connect water pipe bond within first five feet where water pipe enters. Finish labeling panel circuitry after power has been reinstated
|