Final | 12/16/2011 | 12/16/2011 | 12/16/2011 | P | PASS |
Jack Frank
|
|
|
Phone #: ###-#### >> Inspection requested via web by Kathy Smith ok
|
Rough-In Permanent Service | 11/14/2011 | 11/14/2011 | 11/14/2011 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Kathy Smith corrections made, ri ok, p/s u/g n ok
|
Rough-In Permanent Service | 11/11/2011 | 11/14/2011 | 11/14/2011 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Kathy Smith called, left correction notice, NEC 210.52(A)(1) no point along wall shall be over 6 ' from outlet (stairs), 334.30 nm cable shall be secured within 12" of panel, 314.17(c) 8" box in garage, 334.23 shall protect cable within 6' of attic access in garage
|