Final | 12/27/2011 | 12/27/2011 | 12/27/2011 | P | PASS |
Daryl DeGrange
|
|
|
Dan Phone #: ###-#### final ok correction done
|
Final | 12/23/2011 | 12/23/2011 | 12/23/2011 | P | FAIL |
Daryl DeGrange
|
|
|
4 wire dryer and range outlets installed , need final Phone #: ###-#### >> Inspection requested via web by Dan Hobdey Shall separate neutrals and grounds, provide grounding bushing on service racewway, bond with #6 cu to ground bar
|
Permanent Service | 12/23/2011 | 12/23/2011 | 12/23/2011 | A | PASS |
Daryl DeGrange
|
|
|
p/s o/h rec ok
|
Final | 12/22/2011 | 12/23/2011 | 12/23/2011 | A | NR |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Dan Hobdey not ready should of been scheduled for permanet service
|