Final | 1/11/2012 | 1/12/2012 | 1/12/2012 | A | PASS |
Daryl DeGrange
|
|
|
The access code is 3580, any questions please call,TW. Phone #: ###-#### >> Inspection requested via web by Stephen Kren final ok
|
Permanent Service | 1/3/2012 | 1/4/2012 | 1/4/2012 | A | PASS |
Daryl DeGrange
|
|
|
All corrections have been performed, the access code is 3580. Phone #: ###-#### >> Inspection requested via web by Stephen Kren NEC 250.64(B) Requires exsposed grounding electrode conductor to be securely fastened to the surface on which it is carried. Remove hot tub conduit
|
Permanent Service | 12/29/2011 | 12/30/2011 | 12/30/2011 | A | FAIL |
Doug A Poedy
|
|
|
All corrections repaired, please call for any questions, the access code is 3580, thx, TW. Phone #: ###-#### >> Inspection requested via web by Stephen Kren. Water pipe bond and hot and cold jumper needs to be installed
|
Permanent Service | 12/23/2011 | 12/23/2011 | 12/27/2011 | P | FAIL |
Doug A Poedy
|
|
|
There hasn''t been a meter at this location for over a year, Idaho Power is requiring an inspection of the service before powering, the access code is 3580, thanks. Phone #: ###-#### >> Inspection requested via web by Stephen Kren. All wiring to sub-panel and hot tub nedds to be removed or brought up to code. Grounding and bonding brought up to code. All holes in sevice panel plugged.
|