Final | 2/24/2012 | 2/27/2012 | 2/27/2012 | A | PASS |
Jack Frank
|
|
|
GARAGE CODE 10020 Phone #: ###-#### >> Inspection requested via web by Bob Glenn ok
|
Rough-In Permanent Service | 1/11/2012 | 1/12/2012 | 1/12/2012 | A | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Bob Glenn correction done rough-in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 1/11/2012 | 1/11/2012 | 1/11/2012 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Bob Glenn n called, left correction notice, NEC 300.4 shall provide nail plates- garage, misc, 210.52(E)(1) shall provide outlet at rear of dwelling, 334.23 shall protect nm cable within 6' of attic access, BCC shall provide box for closet luminaire
|