Final | 4/20/2012 | 4/23/2012 | 4/23/2012 | A | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Phil Baker final ok
|
Final | 4/19/2012 | 4/20/2012 | 4/20/2012 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Phil Baker called, left correction notice, NEC 240.4 shall protect a/c per nameplate (20 A) max, 110.22 shall label disconnects with marking sufficient for environment and label panels correctly, 334.15(C) shall protect nm cable in unfinished basement and provide raceway at water heater
|
Electrical Rough-In | 1/20/2012 | 1/20/2012 | 1/20/2012 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Phil Baker rough-in ok cover addition & upstairs remodel
|
Permanent Service | 1/17/2012 | 1/17/2012 | 1/17/2012 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Phil Baker p/s o/h rec ok check water pipe bonding on r/i plumbing contractor installing poly pipe
|