Final | 1/16/2012 | 1/17/2012 | 1/17/2012 | P | PASS |
Daryl DeGrange
|
|
|
Contact Mike Jensen Phone #: ###-#### >> Inspection requested via web by Cozzett Allen t/s u/g n ok
|
Temporary Service | 1/11/2012 | 1/11/2012 | 1/11/2012 | P | FAIL |
Daryl DeGrange
|
|
|
Contact is Mike Jensen Phone #: ###-#### >> Inspection requested via web by Cozzett Allen NEC 250.53 where rock bottom is incountered the electrode shall be permited to be buried in a trench that is at least 30 inches deep.The upper end of the electrode shall be flush with or belowground level. Label receptacles with what breaker
|