Final | 3/18/2012 | 3/19/2012 | 3/19/2012 | P | PASS |
Bob Reichert
|
|
|
Finel. Ryan is contact. Thanks Phone #: ###-#### >> Inspection requested via web by Chris Chesnut ok final
|
Rough-In Permanent Service | 1/27/2012 | 1/27/2012 | 1/27/2012 | P | PASS |
Bob Reichert
|
|
|
Re-inspect. Ryan is contact. Thank you Phone #: ###-#### >> Inspection requested via web by Chris Chesnut corrections made, ri ok, p/s u/g n ok
|
Rough-In Permanent Service | 1/26/2012 | 1/27/2012 | 1/27/2012 | A | FAIL |
Bob Reichert
|
|
|
Ryan is contact. Sorry about the back to back days. Have a good weekend and thanks. Phone #: ###-#### >> Inspection requested via web by Chris Chesnut called, left correction notice, NEC 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members, 334.30 shall staple nm within 12" of panel, 250.86 shall ground metal boxes, 410.16(C) shall verify clothes closet fixtures provide clearance, BCC all make-up shall be done, shall provide boxes for nm cable, shall change room count on permit to 24 rooms
|
Electrical Rough-In | 1/25/2012 | 1/26/2012 | 1/26/2012 | A | PASS |
Bob Reichert
|
|
|
PARTIAL rough in. Didn''t give me that option. SOFFIT inspection. Ryan is contact. Thank you Phone #: ###-#### >> Inspection requested via web by Chris Chesnut ok cover soffits only
|