Final | 3/16/2012 | 3/19/2012 | 3/19/2012 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Michael Hagerty ok final
|
Electrical Rough-In | 2/15/2012 | 2/15/2012 | 2/16/2012 | P | PASS |
Bob Reichert
|
|
|
mike Phone #: ###-#### corrections made, ok cover u/g
|
Electrical Rough-In | 2/14/2012 | 2/14/2012 | 2/14/2012 | P | FAIL |
Bob Reichert
|
|
|
mike called, left message, left correction notice, NEC 342.26 there shall not be over 360 degree bend in raceway
|
Electrical Rough-In | 2/9/2012 | 2/9/2012 | 2/9/2012 | P | FAIL |
Bob Reichert
|
|
|
mike Phone #: ###-#### called, main n-s u/g only ok cover, need to see terminations prior to cover, left correction notice, BCC 4-05-33(A)(B) all equipment shall be listed by a nationally recognized testing laboratory, NEC 110.3 listed or labelled equipment shall be installed in accordance with included instructions, 500.4 shall supply area classification drawing
|