Final | 3/28/2012 | 3/29/2012 | 3/29/2012 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Clint Tate corrections made, ok final, signed card
|
Final | 3/22/2012 | 3/23/2012 | 3/23/2012 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Clint Tate met electrician, left correction notice, BCC 4-05-33(A),(B)shall provide listing for walk-in cooler by a nationally recognized testing laboratory, BCC no violations shall be retained, NEC 330.30(B) shall secure mc cable within 12" of box, 725.25 shall remove abandoned lv cable, 300.11 cables and raceways shall not be supported by ceiling grid or tile
|
Electrical Rough-In | 2/22/2012 | 2/22/2012 | 2/22/2012 | P | PASS |
Bob Reichert
|
|
|
Wall, Re-inspect Phone #: ###-#### >> Inspection requested via web by Clint Tate walls only ok cover
|
Electrical Rough-In | 2/21/2012 | 2/22/2012 | 2/22/2012 | A | NH |
Bob Reichert
|
|
|
Wall Phone #: ###-#### >> Inspection requested via web by Clint Tate met electrician, no access, fee due
|