Final | 4/25/2012 | 4/25/2012 | 4/25/2012 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI ok final
|
Rough-In Permanent Service | 3/21/2012 | 3/21/2012 | 3/21/2012 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI corrections made, ri ok, p/s u/g n ok
|
Rough-In Permanent Service | 3/20/2012 | 3/21/2012 | 3/21/2012 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI called, left correction notice, NEC 324.23 shall protect cable within 6' of attic access, 300.4 edge of bored hole shall be 1 1/4" from edge of framing member, 314.17(C) shall secure nm cale within 8" of box, 110.12(B) there shall be no broken boxes
|