Final | 4/11/2012 | 4/11/2012 | 4/11/2012 | P | PASS |
Jack Frank
|
|
|
Dwayne is the electrician Phone #: ###-#### >> Inspection requested via web by joel smith
|
Permanent Service | 4/6/2012 | 4/9/2012 | 4/9/2012 | A | PASS |
Daryl DeGrange
|
|
|
Electrician is Dwayne. Phone #: ###-#### >> Inspection requested via web by joel smith p/s u/g n ok
|
Conference | 4/4/2012 | 4/5/2012 | 4/5/2012 | A | PASS |
Daryl DeGrange
|
|
|
would like to request a conference on site with Doug Poedy, 9:00 or 9:30 if available. Please call Mike Johnson. Phone #: ###-#### >> Inspection requested via web by joel smith Conference / rough-in ok cover trench
|
Permanent Service | 3/28/2012 | 3/29/2012 | 3/29/2012 | A | FAIL |
Jack Frank
|
|
|
for Hickories Sub pump skid. nearest address to the sub is 5284 N Farrow(5 mile & Mcmillan area). Phone #: ###-#### >> Inspection requested via web by joel smith called left message correction posted 110.9&10 fault current levels, 250.32 grd rods at pump p/sand grd or bond metal piping, also shall address it as sevice equip. 225.30,31,32,33,36 BCC4-5-41,42 u/g conduit covered without inspection
|