Final | 4/18/2012 | 4/18/2012 | 4/18/2012 | A | PASS |
Bob Reichert
|
|
|
call for access code Phone #: ###-#### >> Inspection requested via web by Rick Beckman ok final, signed card
|
Electrical Rough-In | 4/18/2012 | 4/18/2012 | 4/18/2012 | A | PASS |
Bob Reichert
|
|
|
ceiling inspection, call for access Phone #: ###-#### >> Inspection requested via web by Rick Beckman ok cover ceiling
|
Rough-In Permanent Service | 3/28/2012 | 3/28/2012 | 3/28/2012 | P | PASS |
Bob Reichert
|
|
|
call for access Phone #: ###-#### >> Inspection requested via web by Rick Beckman corrections made, ri ok, p/s, exst meter pak, n, ok
|
Rough-In Permanent Service | 3/27/2012 | 3/28/2012 | 3/28/2012 | A | FAIL |
Bob Reichert
|
|
|
Call for access code. Phone #: ###-#### >> Inspection requested via web by Rick Beckmancalled, NEC shall secure mc per 330.30, shall not have foreign system over panel per NEC 110.26(F)(1)(b) , shall identify main breaker
|