Final | 5/23/2012 | 5/24/2012 | 5/24/2012 | A | PASS |
Daryl DeGrange
|
|
|
For access call owner at ###-#### Phone #: ###-#### >> Inspection requested via web by Lars Johnson final ok
|
Final | 4/20/2012 | 4/23/2012 | 4/23/2012 | A | NR |
Daryl DeGrange
|
|
|
Addition of main disconnect on house. Phone #: ###-#### >> Inspection requested via web by Lars Johnson
|
Permanent Service | 4/23/2012 | 4/23/2012 | 4/23/2012 | A | FAIL |
Daryl DeGrange
|
|
|
Permanent service NEC 250.32 Requires four wire system from disconect on outside of house to indoor panel, with separation of grounds and neutrals
|
Electrical Rough-In | 4/23/2012 | 4/23/2012 | 4/23/2012 | A | PASS |
Daryl DeGrange
|
|
|
rough-in ok cover ground rods- pour concrete
|