Final | 7/11/2012 | 7/12/2012 | 7/12/2012 | A | PASS |
Bob Reichert
|
|
|
Call Dene with any questions Thank you Phone #: ###-#### >> Inspection requested via web by kim grundhauser ok final
|
Final | 7/10/2012 | 7/10/2012 | 7/10/2012 | A | FAIL |
Bob Reichert
|
|
|
Call Dene with any questions Thank you Phone #: ###-#### >> Inspection requested via web by kim grundhauser shall add outlet in mbr north wall, stair lights shall operate, will recall, called contractor
|
Rough-In Permanent Service | 5/9/2012 | 5/10/2012 | 5/9/2012 | A | PASS |
Bob Reichert
|
|
|
Call Dene with any questions Thank you Phone #: ###-#### >> Inspection requested via web by kim grundhauser corrections made, ri ok, p/s u/g n ok
|
Rough-In Permanent Service | 5/8/2012 | 5/8/2012 | 5/8/2012 | A | FAIL |
Bob Reichert
|
|
|
Call Dene with any questions Thank you Phone #: ###-#### >> Inspection requested via web by kim grundhauser called, left correction notice3, NEC 110.26(F)(1) shall not install foreign piping in dedicated electrical space, 334.23 shall protect cables within 6' of attic accesses, 300.4(D) shall provide 1 1/4" from edge of framing members to edge of ent, BCC shall install garage lights, make-up mbr receptacles, install framing members
|