Final | 1/20/2016 | 1/21/2016 | 1/21/2016 | A | PASS |
Bob Reichert
|
|
|
Fixed service as per inspection Phone #: ###-#### Inspection requested via web by robert feller corrections made, ok final
|
ELE-Aging Inspection | 1/5/2016 | 1/5/2016 | 1/7/2016 | | DONE |
Rex Boyles
|
|
|
spoke with Bob and he is following up on this
|
ELE-Aging Inspection | 10/6/2015 | 10/6/2015 | 10/8/2015 | | DONE |
Rex Boyles
|
|
|
too busy
|
ELE-Aging Inspection | 7/7/2015 | 7/7/2015 | 7/7/2015 | | DONE |
Rex Boyles
|
|
|
called office but in fax machine mode
|
ELE-Aging Inspection | 4/7/2015 | 4/7/2015 | 4/7/2015 | | DONE |
Rex Boyles
|
|
|
too busy
|
Final | 1/6/2015 | 1/6/2015 | 1/6/2015 | P | FAIL |
Rex Boyles
|
|
|
Call owner Jill Young to get access into house phone number ###-#### Phone #: ###-#### Inspection requested via web by robert feller Relocate 100 amp breaker at lowest position in all in one, 2" strap on riser, identify panel in basement.
|
Final | 1/5/2015 | 1/6/2015 | 1/6/2015 | A | NH |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by robert feller No access Left note on window for owner to contact electrical contractor
|
ELE-Aging Inspection | 1/5/2015 | 1/5/2015 | 1/5/2015 | | DONE |
Rex Boyles
|
|
|
Bob will call it in
|
ELE-Aging Inspection | 10/6/2014 | 10/6/2014 | 10/6/2014 | | DONE |
Rock A. Hudson
|
|
|
Waiting on owner
|
ELE-Aging Inspection | 7/7/2014 | 7/7/2014 | 7/7/2014 | | DONE |
Rock A. Hudson
|
|
|
Still under construction
|
ELE-Aging Inspection | 3/27/2014 | 3/27/2014 | 4/4/2014 | | CANC |
Bob Reichert
|
|
|
|
ELE-Aging Inspection | 12/26/2013 | 12/26/2013 | 12/27/2013 | | DONE |
Bob Reichert
|
|
|
called to have contractor call for final
|
ELE-Aging Inspection | 9/26/2013 | 9/26/2013 | 9/30/2013 | | CANC |
Bob Reichert
|
|
|
|
Electrical Rough-In | 5/29/2012 | 5/30/2012 | 5/30/2012 | A | PASS |
Bob Reichert
|
|
|
Bob Phone #: ###-#### corrections made, ri ok house part only
|
Electrical Rough-In | 5/29/2012 | 5/29/2012 | 5/29/2012 | P | FAIL |
Daryl DeGrange
|
|
|
bob Phone #: ###-#### NEC 314.20 Outside fixture boxes mounted in walls constructed of wood shall be flush with surface NEC334.30 NM cable shall be stapled within 8 in of box, 12 in. if box has loom clamps
|
Final | 5/22/2012 | 5/25/2012 | 5/25/2012 | A | NR |
Doug A Poedy
|
|
|
Phone #: ###-#### >> Inspection requested via web by robert feller
|
Permanent Service | 5/22/2012 | 5/23/2012 | 5/23/2012 | A | PASS |
Bob Reichert
|
|
|
Bob Phone #: ###-#### p/s o/h rec ok
|