Final | 2/21/2013 | 2/22/2013 | 2/22/2013 | A | PASS |
Rock A. Hudson
|
|
|
Eric Phone #: ###-#### Corrections made. Final ok
|
Final | 2/20/2013 | 2/20/2013 | 2/20/2013 | P | FAIL |
Rock A. Hudson
|
|
|
eric Phone #: ###-#### Weather proof in use cover needed for up deck receptical. Up blue bed open ground on circuit. Up white bed smoke detector power cold. Straps required on AC whip. Miss wire at AC disconnect, line/ load. Lock out or disconnect required for water heater circuit. Insulating bushing needed for flourescent fixture over stair to basement.
|
Electrical Rough-In | 10/8/2012 | 10/8/2012 | 10/8/2012 | P | PASS |
Rock A. Hudson
|
|
|
Eric Phone #: ###-#### Rough in ok cover
|
Electrical Rough-In | 9/28/2012 | 9/28/2012 | 9/28/2012 | P | NR |
Rock A. Hudson
|
|
|
eric Phone #: ###-#### Will Call When Ready
|
Permanent Service | 6/15/2012 | 6/15/2012 | 6/15/2012 | P | PASS |
Daryl DeGrange
|
|
|
eric Phone #: ###-#### p/s o/h rec ok
|
Conference | 6/13/2012 | 6/13/2012 | 6/13/2012 | P | PASS |
Daryl DeGrange
|
|
|
Eric Phone #: ###-#### Discussed with home owner about requirements for remote service from detached garage
|
Conference | 5/31/2012 | 5/31/2012 | 5/31/2012 | P | PASS |
Daryl DeGrange
|
|
|
call when on way//Eric Phone #: ###-#### Discussed requirements for remodeling single family dwelling
|