Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberELE12-01340
StatusFinaled
Name ALLOWAY ELECTRIC CO INC
Site Address 5310 W DENTON ST
Project Name 
Customer Number56064
ePlanReviewNo
Description
Electrical Permit - Repair: mast pulled away from house.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/5/201211/5/201211/5/2012PPASS
DetailsBob Reichert
phone # of above, cust will be home, just knock on door to gain access inside Phone #: ###-#### >> Inspection requested via web by joel smith ok final
Final6/7/20126/8/20126/7/2012ACANC
DetailsJack Frank
inspection to get customer''s power on. Customer will need to make electrical repairs within 3 mo. to keep power on. Phone #: ###-#### >> Inspection requested via web by joel smith
see added t/s
Temporary Service6/7/20126/7/20126/7/2012PPASS
DetailsJack Frank
power allowed on t/s basis only, owner has 3 months to correct all wiring done in violation of prior and current N.E.C. per acti ng PDS director Hal Simmons. #!230.6 service entrance conductors shall be installed outside of building, or encased in 2"of concrete or brick, #2 230.70(A)(1) shall install service disconnect either outside of a building,or nearest the point of entrance of the service conductors ( back to back) #3 250.24 (A)(5) shall isolated grounding, and neutrals load side of service main, inside panel shall be addressed as subpanel. #4 250.134,250.138 shall provide 4wire branch circuit, receptacle, and pigtail for range and dryer fed from subpanel #5 250.24 all main grounding and bonding conductors shall connect to the neutral service conductor bus at the main service , not subpanel

t/s o/h rec. ok
Rough-In Permanent Service6/6/20126/7/20126/7/2012ANR
DetailsJack Frank
Brandon is the electrician. Ready to final. Phone #: ###-#### >> Inspection requested via web by joel smith talked with contr they will request inspection when ready
Permanent Service6/6/20126/6/20126/6/2012PFAIL
DetailsJack Frank
Brandon is the electrician. Ready to final. Phone #: ###-#### >> Inspection requested via web by joel smith note no violation to be retained original p/s install in violation of NEC service entrance conductors shall be outside or considered outside 230.6, old p/s will now be subpanel address grding and bonding to new p/s , also address range and dryer branch circuits 4 wire