Final | 11/5/2012 | 11/5/2012 | 11/5/2012 | P | PASS |
Bob Reichert
|
|
|
phone # of above, cust will be home, just knock on door to gain access inside Phone #: ###-#### >> Inspection requested via web by joel smith ok final
|
Final | 6/7/2012 | 6/8/2012 | 6/7/2012 | A | CANC |
Jack Frank
|
|
|
inspection to get customer''s power on. Customer will need to make electrical repairs within 3 mo. to keep power on. Phone #: ###-#### >> Inspection requested via web by joel smith see added t/s
|
Temporary Service | 6/7/2012 | 6/7/2012 | 6/7/2012 | P | PASS |
Jack Frank
|
|
|
power allowed on t/s basis only, owner has 3 months to correct all wiring done in violation of prior and current N.E.C. per acti ng PDS director Hal Simmons. #!230.6 service entrance conductors shall be installed outside of building, or encased in 2"of concrete or brick, #2 230.70(A)(1) shall install service disconnect either outside of a building,or nearest the point of entrance of the service conductors ( back to back) #3 250.24 (A)(5) shall isolated grounding, and neutrals load side of service main, inside panel shall be addressed as subpanel. #4 250.134,250.138 shall provide 4wire branch circuit, receptacle, and pigtail for range and dryer fed from subpanel #5 250.24 all main grounding and bonding conductors shall connect to the neutral service conductor bus at the main service , not subpanel
t/s o/h rec. ok
|
Rough-In Permanent Service | 6/6/2012 | 6/7/2012 | 6/7/2012 | A | NR |
Jack Frank
|
|
|
Brandon is the electrician. Ready to final. Phone #: ###-#### >> Inspection requested via web by joel smith talked with contr they will request inspection when ready
|
Permanent Service | 6/6/2012 | 6/6/2012 | 6/6/2012 | P | FAIL |
Jack Frank
|
|
|
Brandon is the electrician. Ready to final. Phone #: ###-#### >> Inspection requested via web by joel smith note no violation to be retained original p/s install in violation of NEC service entrance conductors shall be outside or considered outside 230.6, old p/s will now be subpanel address grding and bonding to new p/s , also address range and dryer branch circuits 4 wire
|