Final | 11/6/2012 | 11/7/2012 | 11/7/2012 | A | PASS |
Rock A. Hudson
|
|
|
Tom Phone #: ###-#### final ok
|
Final | 11/1/2012 | 11/1/2012 | 11/1/2012 | P | FAIL |
Rock A. Hudson
|
|
|
TOM Phone #: ###-#### 210.52 (B) (5) ex. Receptical mounted below counter top in accordance with this exception shall not be located where the counter top extends more than 6 inches beyond its base. peninsular 352.30 (B) Underground service riser shall be supported with in 3' of meter base.
|
Rough-In Permanent Service | 8/9/2012 | 8/9/2012 | 8/9/2012 | P | PASS |
Daryl DeGrange
|
|
|
Eric Phone #: ###-#### rough-in p/s u/g n ok
|
Rough-In Permanent Service | 8/9/2012 | 8/9/2012 | 8/9/2012 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Eric Brown rough-in p/s u/g n ok
|
Electrical Rough-In | 6/20/2012 | 6/20/2012 | 6/20/2012 | P | PASS |
Daryl DeGrange
|
|
|
under slab trench inspection mike cole Phone #: ###-#### >> Inspection requested via web by mike brown rough-in ok cover under slab
|