Permit Information
Permit NumberELE12-01638
StatusFinaled
Name R M E INC
Site Address 401 S BROADWAY AVE
Project NameWhole Foods
Customer Number 
ePlanReviewNo
Description
Electrical Permit - New: Install light fixtures & gear per plans.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/7/201211/7/201211/7/2012PPASS
DetailsRock A. Hudson
Steve. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy 2000 amp main load test completed by Current Technologies Job # 2012266 Passed Final ok
Conference11/5/201211/6/201211/6/2012PDONE
DetailsRock A. Hudson
Steve. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy Signed temp occupancy, need drip protection over panels in mechanical room. All other corrections have been improved. Rocky Mountain Electric Job # 2012266, 2000 amp main load test pass
Final11/2/201211/2/201211/2/2012PPART
DetailsRock A. Hudson
Steve. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy All main floor ok, food prep areas ok,
Items needed- 1. Any 480v Y system rated 1000 amps or more shall be tested by certified 3rd party testing company and a copy of compiance shall be on site as well as filed with the city of Boise, 2. Arc flash labelling shall be on all panel boards and disconnects, 3. Show control boxes on outdoor compactors NEMA 3R rated. 4. Refrigeration compressor assembly disconnect shall be located in a readily accessible location, 6' 7' to top of handle.
Final10/29/201210/30/201210/30/2012PNR
DetailsBob Reichert
Steve. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy met with 327 and 445 along with contractor, shall provide code sized pull boxes, gfci's, clearances about equipment, listed equipment, support raceways, weather proof operators, shall be ready before call for inspection, agreed to do part inspection because of changes and new permit being pulled, fee due
Final10/19/201210/22/201210/22/2012ACANC
DetailsRock A. Hudson
Steve Phone #: ###-#### >> Inspection requested via web by Sean DeLacy
Electrical Rough-In10/22/201210/22/201210/22/2012APASS
DetailsRock A. Hudson
Steve. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy Service area meat and fish ceiling rough in ok cover
Electrical Rough-In10/19/201210/19/201210/19/2012PNR
DetailsBob Reichert
Steve. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy met contractor, ceiling wires for fixtures not installed, will recall
Final10/17/201210/19/201210/19/2012PCANC
DetailsRock A. Hudson
Steve. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy Inspection cancelled from web by: Sean DeLacy
Electrical Rough-In10/12/201210/12/201210/12/2012PPASS
DetailsRock A. Hudson
Steve. Bakery ceiling cover. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy Bakery ceiling rough in ok cover
Electrical Rough-In10/11/201210/11/201210/11/2012PPASS
DetailsRock A. Hudson
Steve. PM. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy Secondary entry and juice bar ceiling rough in ok cover
Electrical Rough-In10/3/201210/4/201210/4/2012APASS
DetailsRock A. Hudson
Steve. Wall cover. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy Mezz. ceiling rough in cover ok
Electrical Rough-In10/2/201210/3/201210/3/2012ANR
DetailsBob Reichert
Steve. Ceiling Cover. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy shall finish strapping branch circuits in upstairs ceiling
Electrical Rough-In9/26/20129/27/20129/26/2012APART
DetailsDoug A Poedy
Steve. Wall cover. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy. Marked on prints.
Electrical Rough-In9/24/20129/25/20129/25/2012APASS
DetailsRock A. Hudson
Steve. Service meat department. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy Meat fish ceiling ok cover
Permanent Service9/13/20129/14/20129/14/2012APASS
DetailsDaryl DeGrange
Steve is on site. Phone #: ###-#### >> Inspection requested via web by Buster Bowen p/s u/g n ok panel borad
Electrical Rough-In9/11/20129/11/20129/11/2012PPASS
DetailsDaryl DeGrange
Steve is on site. Ceiling cover for Mezz Phone #: ###-#### >> Inspection requested via web by Buster Bowen rough-in ok cover mezzanine hard lid
Electrical Rough-In9/7/20129/7/20129/7/2012APASS
DetailsDaryl DeGrange
Steve. Ceiling Cover. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy rough-in ok cover hard lid Bakerey' Deli
Electrical Rough-In8/30/20128/31/20128/31/2012APASS
DetailsDaryl DeGrange
Steve. Bakery wall cover. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy rough-in ok cover Bakery walls & meat,fish walls
Conference8/20/20128/21/20128/21/2012APASS
DetailsDaryl DeGrange
Steve. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy Discuss service grounding and bonding
Electrical Rough-In8/20/20128/20/20128/20/2012APASS
DetailsDaryl DeGrange
Steve. Wall cover. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy rough-in ok cover 2nd floor westside of hallway up to bathrooms, walls only
Electrical Rough-In8/13/20128/14/20128/14/2012APASS
DetailsDaryl DeGrange
wall cover for the west exterior wall and the north half of the mezzanine. Steve is the contact Phone #: ###-#### >> Inspection requested via web by Buster Bowen rough-in ok cover
Electrical Rough-In8/7/20128/8/20128/8/2012APASS
DetailsDaryl DeGrange
Steve. Underground. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy rough-in ok cover remainder of concrete slab
Electrical Rough-In8/6/20128/6/20128/6/2012APART
DetailsDaryl DeGrange
Steve. Underground. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy rough-in ok cover walker duct as per marked and dated on plans
Electrical Rough-In8/2/20128/2/20128/2/2012APART
DetailsBob Reichert
Steve. Underground. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy u/g ok anop
Electrical Rough-In7/30/20127/30/20127/30/2012PPASS
DetailsDaryl DeGrange
STEVE. UNDERGROUND. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy rough-in ok cover underground, back of building #30 Bakery #31 corner area between
Electrical Rough-In7/18/20127/18/20127/18/2012PPASS
DetailsDaryl DeGrange
Steve. Underground. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy rough-in ok cover underground branch circuit conduits from bakery panel
Electrical Rough-In7/10/20127/11/20127/11/2012APASS
DetailsDaryl DeGrange
Steve. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy rough-in ok cover interior underground service conduits
Final7/9/20127/10/20127/10/2012PCANC
DetailsBob Reichert
Toby Phone #: ###-#### >> Inspection requested via web by Sean DeLacy wrong permit and request, called, they will recall
Electrical Rough-In7/3/20127/5/20127/5/2012APASS
DetailsDaryl DeGrange
Steve. Underground. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy rough-in ok cover interror underground (slab)