Final | 7/24/2012 | 7/25/2012 | 7/25/2012 | A | PASS |
Bob Reichert
|
|
|
Dennis Phone #: ###-#### ok final
|
Permanent Service | 7/16/2012 | 7/17/2012 | 7/17/2012 | A | PASS |
Bob Reichert
|
|
|
Dennis Phone #: ###-#### p/s o/h rec ok
|
Permanent Service | 7/13/2012 | 7/16/2012 | 7/16/2012 | A | FAIL |
Jack Frank
|
|
|
Dennis Phone #: ###-####called shall not use res in service mast needs acorn clamp for grd rod, terminate water bond at p/s not subpanel
|
Conference | 7/10/2012 | 7/10/2012 | 7/10/2012 | P | DONE |
Jack Frank
|
|
|
explained NEC requirements also owner needs to add 3 rms to permit, also needs PLM & MECH permits
|
Conference | 7/9/2012 | 7/10/2012 | 7/10/2012 | A | NH |
Jack Frank
|
|
|
Dennis ###-#### notice posted called will meet in the PM
|