Final | 9/13/2012 | 9/13/2012 | 9/13/2012 | P | PASS |
Daryl DeGrange
|
|
|
Doug Phone #: ###-#### corrections done final ok
|
Final | 9/12/2012 | 9/12/2012 | 9/12/2012 | P | FAIL |
Daryl DeGrange
|
|
|
aaron Phone #: ###-#### NEC 210.8 (B) (2) Kitchens All 125 volt 15 and 20 ampere receptacle in nondwelling-type kitchens to be GFCI protected
|
Permanent Service | 9/5/2012 | 9/6/2012 | 9/5/2012 | A | PASS |
Daryl DeGrange
|
|
|
Doug Phone #: ###-#### corrections none p/s u/g rec ok
|
Permanent Service | 9/4/2012 | 9/5/2012 | 9/5/2012 | A | FAIL |
Daryl DeGrange
|
|
|
Doug Phone #: ###-#### Need to install bushing on service feeders in service disconnect. Terminate equipment grounding conductor in ground bar in sub panel
|
Electrical Rough-In | 8/27/2012 | 8/28/2012 | 8/28/2012 | A | PASS |
Daryl DeGrange
|
|
|
partial r/i for cover//Doug Phone #: ###-#### rough-in ok cover ceiling grid
|
Electrical Rough-In | 7/26/2012 | 7/26/2012 | 7/26/2012 | P | PASS |
Daryl DeGrange
|
|
|
Jason Phone #: ###-#### rough-in ok cover walls
|