Final | 11/6/2013 | 11/6/2013 | 11/6/2013 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton job complete, final ok
|
Final | 10/31/2013 | 11/1/2013 | 11/1/2013 | A | PART |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton Partial final for Toyota sales floor ok Open pull boxes above restroom ceiling, panel directories not complete
|
Electrical Rough-In | 10/28/2013 | 10/28/2013 | 10/28/2013 | P | PASS |
Daryl DeGrange
|
|
|
Grid Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton rough-in ok cover remainder of ceiling grid sale floor.
|
Final | 10/25/2013 | 10/25/2013 | 10/25/2013 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton rough-in ok cover ceiling grid in continued sales floor only
|
Electrical Rough-In | 10/25/2013 | 10/25/2013 | 10/25/2013 | P | CANC |
Daryl DeGrange
|
|
|
Grid Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton Inspection cancelled from web by: Kerri Hamilton
|
Electrical Rough-In | 10/10/2013 | 10/10/2013 | 10/10/2013 | P | PART |
Doug A Poedy
|
|
|
Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton. Walls and hard lid ok.
|
Electrical Rough-In | 10/2/2013 | 10/2/2013 | 10/2/2013 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton Rough-in ok cover under slab floor boxes, 3 locations
|
Final | 9/20/2013 | 9/20/2013 | 9/20/2013 | P | PART |
Daryl DeGrange
|
|
|
Partial final customer lounge area Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton partial final ok
|
Electrical Rough-In | 9/16/2013 | 9/16/2013 | 9/16/2013 | P | PASS |
Daryl DeGrange
|
|
|
New Break Room Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton rough-in ok cover hard lid in break room and celing grid customer service lobby
|
Final | 9/13/2013 | 9/13/2013 | 9/13/2013 | P | PART |
Daryl DeGrange
|
|
|
Scion sale and tower sale ok partial final ok
|
Electrical Rough-In | 9/12/2013 | 9/13/2013 | 9/13/2013 | P | FAIL |
Daryl DeGrange
|
|
|
Rough, Ceiling and Temporary Final Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton open junction boxes, KO pug, receptacles above grid
|
Electrical Rough-In | 9/5/2013 | 9/6/2013 | 9/6/2013 | P | PASS |
Daryl DeGrange
|
|
|
Scion and showroom Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton rough-in ok cover ceiling grid, in both areas
|
Electrical Rough-In | 9/4/2013 | 9/5/2013 | 9/5/2013 | A | FAIL |
Daryl DeGrange
|
|
|
Ceiling in Scion Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton NEC 300.11 (A) Cables and raceways shall not be supported by ceiling grid. NEC 800. The accessible portion of abandoned communications cables shall be removed
|
Electrical Rough-In | 7/19/2013 | 7/22/2013 | 7/22/2013 | A | PASS |
Daryl DeGrange
|
|
|
Sales Tower Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton rough-in ok cover half walls
|
Electrical Rough-In | 6/28/2013 | 7/1/2013 | 7/1/2013 | A | PASS |
Daryl DeGrange
|
|
|
Can lights in front porch Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton rough-in ok cover front entry soffit
|
Electrical Rough-In | 5/20/2013 | 5/21/2013 | 5/21/2013 | A | PASS |
Daryl DeGrange
|
|
|
Scion Floor Boxes Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton rough-in ok cover 14 floor boxes
|
Electrical Rough-In | 5/2/2013 | 5/2/2013 | 5/2/2013 | A | PASS |
Daryl DeGrange
|
|
|
Ceiling grid/cover - Cameron ###-#### rough-in ok cover ceiling grids egress hallway from accounting office and Lexus service driveway
|
Electrical Rough-In | 4/23/2013 | 4/24/2013 | 4/24/2013 | A | CANC |
Daryl DeGrange
|
|
|
Temp Occupancy in Lexus and Mezzanine Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton
|
Final | 4/24/2013 | 4/24/2013 | 4/24/2013 | A | PASS |
Daryl DeGrange
|
|
|
Temporary occupancy in Lexus and Mezzaine partial final ok No card on site
|
Final | 4/24/2013 | 4/24/2013 | 4/24/2013 | A | CANC |
Daryl DeGrange
|
|
|
Temp. occupancy in Lexus and Mezzaine partial final ok
|
Electrical Rough-In | 4/17/2013 | 4/18/2013 | 4/18/2013 | A | PASS |
Daryl DeGrange
|
|
|
Ceiling in Accounting Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton Rough-in ok cover ceiling grid
|
Electrical Rough-In | 4/3/2013 | 4/4/2013 | 4/4/2013 | P | PASS |
Daryl DeGrange
|
|
|
Ceiling in Lexus Sales Area Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton rough-in ok cover ceiling grid
|
Electrical Rough-In | 2/21/2013 | 2/22/2013 | 2/22/2013 | A | PASS |
Daryl DeGrange
|
|
|
Lexus walls, stairwell to mezzo Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton rough-in ok cover
|
Electrical Rough-In | 2/4/2013 | 2/5/2013 | 2/5/2013 | P | PASS |
Daryl DeGrange
|
|
|
Downstairs mezzanine Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton rough-in ok cover walls
|
Electrical Rough-In | 1/31/2013 | 1/31/2013 | 1/31/2013 | P | PASS |
Daryl DeGrange
|
|
|
Locker Room and Upstairs Mezzanine Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton rough-in ok cover
|
Electrical Rough-In | 1/15/2013 | 1/15/2013 | 1/15/2013 | P | PASS |
Daryl DeGrange
|
|
|
FLOOR BOXES IN SERVICE WRITERS AREA Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton rough-in ok cover UL listed floor boxes
|
Electrical Rough-In | 1/9/2013 | 1/10/2013 | 1/10/2013 | A | PASS |
Daryl DeGrange
|
|
|
Accounting Area Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton rough-in ok cover walls
|
Electrical Rough-In | 10/5/2012 | 10/5/2012 | 10/5/2012 | P | PASS |
Daryl DeGrange
|
|
|
mike Phone #: ###-#### corrections done rough-in ok cover walls and hard lid ceiling, shower-break room near service depart.
|
Electrical Rough-In | 10/4/2012 | 10/4/2012 | 10/4/2012 | P | FAIL |
Doug A Poedy
|
|
|
mike - call when onsite Phone #: ###-####. Strapping issues everywhere.
|
Electrical Rough-In | 9/14/2012 | 9/14/2012 | 9/14/2012 | P | PASS |
Daryl DeGrange
|
|
|
Inspector Bob Reichart needs to come back and re-inspect BMW bathroom and office area walls and ceiling Phone #: ###-#### Phone #: ###-#### >> Inspection requested via web by Chad McKibben rough-in ok cover walls only
|
Electrical Rough-In | 9/12/2012 | 9/13/2012 | 9/13/2012 | A | PART |
Bob Reichert
|
|
|
BMW bathroom and office area walls and ceiling Phone #: ###-#### >> Inspection requested via web by Patrick D Gill center wall and 2 bath ok cover, perimeter wall boxes too small
|