Final | 11/30/2015 | 12/1/2015 | 12/1/2015 | A | PASS |
Rex Boyles
|
|
|
Rudy// please call before for access Phone #: ###-#### corrections made final ok
|
Final | 11/6/2015 | 11/6/2015 | 11/6/2015 | P | NH |
Rex Boyles
|
|
|
Call for access // Rudy Phone #: ###-#### no access called and left message
|
Final | 9/1/2015 | 9/14/2015 | 9/14/2015 | P | FAIL |
Rex Boyles
|
|
|
Rudy-###-#### Clyde smart cell ###-#### 210.8(A)(7)- GFCI protection required within 6 foot of sinks. 210.12(A)- AFCI protection required in bdrms.(UPST). Garage: Install ground rod for subpanel at garage, ko seals in panel and covers on devices
|
ELE-Aging Inspection | 8/18/2015 | 8/18/2015 | 8/20/2015 | | DONE |
Rex Boyles
|
|
|
called the office and then called cell phone left another message to call for final insp
|
ELE-Aging Inspection | 5/19/2015 | 5/19/2015 | 5/19/2015 | | DONE |
Rex Boyles
|
|
|
left message again
|
ELE-Aging Inspection | 2/17/2015 | 2/17/2015 | 2/20/2015 | | DONE |
Rex Boyles
|
|
|
too busy
|
ELE-Aging Inspection | 11/18/2014 | 11/18/2014 | 11/18/2014 | | DONE |
Rex Boyles
|
|
|
left message
|
ELE-Aging Inspection | 8/19/2014 | 8/19/2014 | 8/21/2014 | | DONE |
Rock A. Hudson
|
|
|
Still under construction
|
ELE-Aging Inspection | 5/20/2014 | 5/20/2014 | 5/22/2014 | | DONE |
Rock A. Hudson
|
|
|
Called left message
|
Electrical Rough-In | 9/13/2012 | 9/14/2012 | 9/14/2012 | P | PASS |
Bob Reichert
|
|
|
Please Call Rudy, the home owner 30 min before inspection so he can come unlock the door. Thanks much. Phone is ###-#### Phone #: ###-#### >> Inspection requested via web by clyde smart ri ok
|