Information based on query as of Wednesday, July 3, 2024.
Permit Information
Permit NumberELE12-02281
StatusFinaled
Name SMART ELECTRIC
Site Address 5200 W DENTON ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/30/201512/1/201512/1/2015APASS
DetailsRex Boyles
Rudy// please call before for access Phone #: ###-#### corrections made final ok
Final11/6/201511/6/201511/6/2015PNH
DetailsRex Boyles
Call for access // Rudy Phone #: ###-#### no access called and left message
Final9/1/20159/14/20159/14/2015PFAIL
DetailsRex Boyles
Rudy-###-#### Clyde smart cell ###-#### 210.8(A)(7)- GFCI protection required within 6 foot of sinks. 210.12(A)- AFCI protection required in bdrms.(UPST). Garage: Install ground rod for subpanel at garage, ko seals in panel and covers on devices
ELE-Aging Inspection8/18/20158/18/20158/20/2015 DONE
DetailsRex Boyles
called the office and then called cell phone left another message to call for final insp
ELE-Aging Inspection5/19/20155/19/20155/19/2015 DONE
DetailsRex Boyles
left message again
ELE-Aging Inspection2/17/20152/17/20152/20/2015 DONE
DetailsRex Boyles
too busy
ELE-Aging Inspection11/18/201411/18/201411/18/2014 DONE
DetailsRex Boyles
left message
ELE-Aging Inspection8/19/20148/19/20148/21/2014 DONE
DetailsRock A. Hudson
Still under construction
ELE-Aging Inspection5/20/20145/20/20145/22/2014 DONE
DetailsRock A. Hudson
Called left message
Electrical Rough-In9/13/20129/14/20129/14/2012PPASS
DetailsBob Reichert
Please Call Rudy, the home owner 30 min before inspection so he can come unlock the door. Thanks much. Phone is ###-#### Phone #: ###-#### >> Inspection requested via web by clyde smart ri ok