Permit Information
Permit NumberELE12-02448
StatusFinaled
Name POWER ELECTRIC
Site Address 980 N MILWAUKEE ST
Project NameMICKEY RAY'S BBQ RESTAURANT
Customer Number 
ePlanReviewNo
Description
Permit for the interior remodel and equipment hook up per initial value of $6500
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/6/201211/6/201211/6/2012PPASS
DetailsBob Reichert
call prior to going Phone #: ###-#### ok final, signed card
Final11/5/201211/5/201211/5/2012PFAIL
DetailsBob Reichert
need atleast 1 hr notice to meet//Warren Phone #: ###-#### shall label panels with circuit directories, rest ok
Final11/2/201211/2/201211/2/2012PFAIL
DetailsDoug A Poedy
WARREN Phone #: ###-####. GFI protection and loose panel covers.
Final10/22/201210/23/201210/23/2012ANR
DetailsDaryl DeGrange
Warren Phone #: ###-####
Final10/16/201210/17/201210/17/2012AFAIL
DetailsDaryl DeGrange
chad Phone #: ###-#### Not all corrections completed
Temporary Service10/15/201210/16/201210/16/2012AFAIL
DetailsRock A. Hudson
Inspection for temporary occupancy. Phone #: ###-#### >> Inspection requested via web by Judy Spencer 314.20 Recepticals not flush with finished surface shall have listed extender. 210.8(B)(1) Outlets in bathrooms shall have GFCI protection. 210.8(B)(5) All outlets with in 6' of a sink shall have GFCI protection. 210.8(B)(2) All 15 and 20 amp recepticals in kitchen area shall have GFCI protection. 314.25 In complete installations each box shall have a cover.
Final10/8/201210/9/201210/9/2012ACANC
DetailsDaryl DeGrange
very early as possible//Warren Phone #: ###-####
Electrical Rough-In10/9/201210/9/201210/9/2012APASS
DetailsDaryl DeGrange
rough-in ok cover interior soffit
Electrical Rough-In10/8/201210/8/201210/8/2012PPASS
DetailsBob Reichert
Ceiling & wall rough-in. Phone #: ###-#### >> Inspection requested via web by Judy Spencer ok cover walls for heat lamps only, will recall for soffit (ceiling)
Electrical Rough-In10/4/201210/4/201210/4/2012PPASS
DetailsDaryl DeGrange
r/i ceiling & amp; Warren Phone #: ###-#### correction done rough-in ok cover walls & hard lid
Electrical Rough-In10/3/201210/4/201210/4/2012AFAIL
DetailsDaryl DeGrange
Rough-in ceiling & wall in one room. Phone #: ###-#### >> Inspection requested via web by Judy Spencer NEC 330.12(1) MC Subject to physical damage Shall not install MC inside steel 2x4 studs