Final | 10/15/2012 | 10/15/2012 | 10/15/2012 | P | PASS |
Bob Reichert
|
|
|
Jeff Creek ###-####. Phone #: ###-#### x0000 >> Inspection requested via web by Andrea Creek ok final
|
Permanent Service | 10/15/2012 | 10/15/2012 | 10/15/2012 | P | PASS |
Bob Reichert
|
|
|
Jeff Creek ###-####. Phone #: ###-#### x0000 >> Inspection requested via web by Andrea Creek p/s u/g rec ok
|
Permanent Service | 10/4/2012 | 10/5/2012 | 10/5/2012 | A | FAIL |
Daryl DeGrange
|
|
|
This house has been off for a yr, need to reenergize. Lockbox code=12468. Jeff Creek ###-####. Phone #: ###-#### >> Inspection requested via web by Andrea Creek Service entrance conduit requires strap within 3 ft. of meter, conductors #4 and larger require bushing in meter main, sub-panel requires all KOs to be filled, branch circuit conductor shall enter through listed connector Locate service electrode grounding conductor connection or drive two new ground rods
|