Final | 3/27/2013 | 3/28/2013 | 3/28/2013 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Rhonda Yoast Final ok
|
Final | 3/27/2013 | 3/27/2013 | 3/27/2013 | P | FAIL |
Rock A. Hudson
|
|
|
Please call Bill if you have any questions Phone #: ###-#### >> Inspection requested via web by Rhonda Yoast 210.8 (A)(6)- Appliance garage- Where recepticals are installed to serve counter top surfaces they shall have GFCI protection. 110.7- Complete wiring installation- bed arcfault breaker will not hold. 110.22 Each disconnecting means shall be marked to indicate its purpose. Due to HVAC code residential garages from floor to 18" above floor shall be considered class 1 division 1 due to fuel storage and lack of air movement. Recepticals shall be installed above 18" from floor
|
Permanent Service | 11/26/2012 | 11/27/2012 | 11/27/2012 | A | PASS |
Rock A. Hudson
|
|
|
Please reinspect service the correction have been made. Phone #: ###-#### >> Inspection requested via web by Rhonda Yoast p/s u/g n ok
|
Rough-In Permanent Service | 11/14/2012 | 11/15/2012 | 11/15/2012 | A | FAIL |
Rock A. Hudson
|
|
|
If you have any question please call Bill at the number listed. Phone #: ###-#### >> Inspection requested via web by Rhonda Yoast Dwelling rough in ok cover perminat service fail- feeders from meter to dixconnects do notserve 100% diversified load so are not allowed to use table 310.15 (B)(6)
|
Electrical Rough-In | 11/15/2012 | 11/15/2012 | 11/15/2012 | P | PASS |
Rock A. Hudson
|
|
|
If you have any question please call Bill at the number listed. Phone #: ###-#### >> Inspection requested via web by Rhonda Yoast Dwelling rough in ok cover
|