Permit Information
Permit NumberELE12-02751
StatusFinaled
Name FALCON ELECTRIC INC
Site Address 1512 N 5TH ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - New: New Electrical
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/27/20133/28/20133/28/2013APASS
DetailsRock A. Hudson
Phone #: ###-#### >> Inspection requested via web by Rhonda Yoast
Final ok
Final3/27/20133/27/20133/27/2013PFAIL
DetailsRock A. Hudson
Please call Bill if you have any questions Phone #: ###-#### >> Inspection requested via web by Rhonda Yoast
210.8 (A)(6)- Appliance garage- Where recepticals are installed to serve counter top surfaces they shall have GFCI protection.
110.7- Complete wiring installation- bed arcfault breaker will not hold.
110.22 Each disconnecting means shall be marked to indicate its purpose.
Due to HVAC code residential garages from floor to 18" above floor shall be considered class 1 division 1 due to fuel storage and lack of air movement. Recepticals shall be installed above 18" from floor
Permanent Service11/26/201211/27/201211/27/2012APASS
DetailsRock A. Hudson
Please reinspect service the correction have been made. Phone #: ###-#### >> Inspection requested via web by Rhonda Yoast p/s u/g n ok
Rough-In Permanent Service11/14/201211/15/201211/15/2012AFAIL
DetailsRock A. Hudson
If you have any question please call Bill at the number listed. Phone #: ###-#### >> Inspection requested via web by Rhonda Yoast Dwelling rough in ok cover perminat service fail- feeders from meter to dixconnects do notserve 100% diversified load so are not allowed to use table 310.15 (B)(6)
Electrical Rough-In11/15/201211/15/201211/15/2012PPASS
DetailsRock A. Hudson
If you have any question please call Bill at the number listed. Phone #: ###-#### >> Inspection requested via web by Rhonda Yoast Dwelling rough in ok cover